Spare switch mechanism and terminal block for BX & BD Vertical Air Break boiler level controls.
Switches must not be used for the direct starting of motors. Contacts should be wired in series with the operating coils of relays, contact starters or solenoid valves, and fused separately.
Single pole double throw operation for:
AC:
Maximum voltage 440V
Maximum current 5A
Minimum power factor 0.4
Maximum power 2000VA
DC Resistive:
Maximum power 100w
Maximum voltage 250v
Maximum current 5A
DC Inductive:
Maximum voltage 250v
*Maximum current 0.5a
Maximum time constant 40ms
Maximum power 100w
*Maximum up to 2A dependent upon time constraints of circuit, consult factory
Country of Origin: United Kingdom